HEP 80MBH Isolation Heat Exchanger Panel

Stk#: 
HEP080P
Short Description: 
HEP80MBH ISOLAT HEATEXCH
Short Description 2: 
PANEL
Status: 
Active
Date Introduced: 
September 22, 2014

The main application of the HEP Isolation Heat Exchanger Panel is to provide single wall isolation between a DHW tank and a heating system. This panel is not a temperature control device. The secondary water temperature is wholly dependent on the temperature of the primary supply water.

The panel is pre-wired to work with an optional DHW priority switch which is mounted outside the panel.

Sequence of operation:

  • When a thermostat calls for heat, its internal 24V contacts close, the auxiliary terminals close, and both pumps turn on.
  • When the requirements of the thermostat are met, the internal contacts of the thermostat open, the auxiliary contacts open, and the pumps stop.
  • Both the primary and secondary pumps are activated once every 24 hours, for 15 minutes, to ensure that potable water in the piping is not stagnant.
  • If the optional DHW priority flow switch is installed and the DHW flow is above the factory setting for this device, the primary pump stops and the auxiliary contacts open. When the DHW flow drops below the factory setting the panel resumes normal operation.